The Code of Federal Regulations (CFR) is the official legal print publication containing the codification of the general and permanent rules published in the Federal Register by the departments and agencies of the Federal Government. The Electronic Code of Federal Regulations (eCFR) is a continuously updated online version of the CFR. It is not an official legal edition of the CFR.

Learn more about the eCFR, its status, and the editorial process.

§ 75.601-1 Short circuit protection; ratings and settings of circuit breakers.

Circuit breakers providing short circuit protection for trailing cables shall be set so as not to exceed the maximum allowable instantaneous settings specified in this section; however, higher settings may be permitted by an authorized representative of the Secretary when he has determined that special applications are justified:

Conductor size AWG or MGM Maximum allowable circuit breaker instantaneous setting (amperes)
14 50
12 75
10 150
8 200
6 300
4 500
3 600
2 800
1 1,000
1/0 1,250
2/0 1,500
3/0 2,000
4/0 2,500
250 2,500
300 2,500
350 2,500
400 2,500
450 2,500
500 2,500