The Code of Federal Regulations (CFR) is the official legal print publication containing the codification of the general and permanent rules published in the Federal Register by the departments and agencies of the Federal Government. The Electronic Code of Federal Regulations (eCFR) is a continuously updated online version of the CFR. It is not an official legal edition of the CFR.

Learn more about the eCFR, its status, and the editorial process.

§ 431.86 Uniform test method for the measurement of energy efficiency of commercial packaged boilers.

(a) Scope. This section provides test procedures, pursuant to the Energy Policy and Conservation Act (EPCA), as amended, which must be followed for measuring the combustion efficiency and/or thermal efficiency of a gas- or oil-fired commercial packaged boiler.

(b) Testing and Calculations. Determine the thermal efficiency or combustion efficiency of commercial packaged boilers by conducting the appropriate test procedure(s) indicated in Table 1 of this section.

Table 1 - Test Requirements for Commercial Packaged Boiler Equipment Classes

Equipment category Subcategory Certified rated input
Btu/h
Standards efficiency metric
(§ 431.87)
Test procedure
(corresponding to
standards efficiency
metric required
by § 431.87)
Hot Water Gas-fired ≥300,000 and ≤2,500,000 Thermal Efficiency Appendix A, Section 2.
Hot Water Gas-fired >2,500,000 Combustion Efficiency Appendix A, Section 3.
Hot Water Oil-fired ≥300,000 and ≤2,500,000 Thermal Efficiency Appendix A, Section 2.
Hot Water Oil-fired >2,500,000 Combustion Efficiency Appendix A, Section 3.
Steam Gas-fired (all*) ≥300,000 and ≤2,500,000 Thermal Efficiency Appendix A, Section 2.
Steam Gas-fired (all*) >2,500,000 and ≤5,000,000 Thermal Efficiency Appendix A, Section 2.
>5,000,000 Thermal Efficiency Appendix A, Section 2.
OR
Appendix A, Section 3 with Section 2.4.3.2.
Steam Oil-fired ≥300,000 and ≤2,500,000 Thermal Efficiency Appendix A, Section 2.
Steam Oil-fired >2,500,000 and ≤5,000,000 Thermal Efficiency Appendix A, Section 2.
>5,000,000 Thermal Efficiency Appendix A, Section 2.
OR
Appendix A, Section 3. with Section 2.4.3.2.

(c) Field Tests. The field test provisions of appendix A may be used only to test a unit of commercial packaged boiler with rated input greater than 5,000,000 Btu/h.

[81 FR 89305, Dec. 9, 2016]