PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS


Subpart 111.55—Switches


Contents
§111.55-1   General.
§111.55-3   Circuit connections.

return arrow Back to Top

§111.55-1   General.

(a) Each switch must meet Article 404 of NFPA NEC 2002 (incorporated by reference; see 46 CFR 110.10-1).

(b) Each switch that is in the weather must be in a watertight enclosure and be externally operable.

[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2003-16630, 73 FR 65198, Oct. 31, 2008]

return arrow Back to Top

§111.55-3   Circuit connections.

The load side of each circuit must be connected to the fuse end of a fused-switch or to the coil end of a circuit breaker, except a generator which is connected to either end of a circuit breaker.