Title 10Chapter IISubchapter DPart 431Subpart F → Subject Group


Title 10: Energy
PART 431—ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND INDUSTRIAL EQUIPMENT
Subpart F—Commercial Air Conditioners and Heat Pumps


Energy Efficiency Standards

§431.97   Energy efficiency standards and their compliance dates.

(a) All basic models of commercial package air-conditioning and heating equipment must be tested for performance using the applicable DOE test procedure in §431.96, be compliant with the applicable standards set forth in paragraphs (b) through (f) of this section, and be certified to the Department under 10 CFR part 429.

(b) Each commercial air conditioner or heat pump (not including single package vertical air conditioners and single package vertical heat pumps, packaged terminal air conditioners and packaged terminal heat pumps, computer room air conditioners, and variable refrigerant flow systems) manufactured starting on the compliance date listed in the corresponding table must meet the applicable minimum energy efficiency standard level(s) set forth in Tables 1 through 6 of this section.

Table 1 to §431.97—Minimum Cooling Efficiency Standards for Air Conditioning and Heating Equipment

[Not including single package vertical air conditioners and single package vertical heat pumps, packaged terminal air conditioners and packaged terminal heat pumps, computer room air conditioners, variable refrigerant flow multi-split air conditioners and heat pumps, and double-duct air-cooled commercial package air conditioning and heating equipment]

Equipment typeCooling capacitySubcategoryHeating typeEfficiency levelCompliance date: Equipment manufactured starting on .  .  .
Small Commercial Package Air Conditioning and Heating Equipment (Air-Cooled, 3-Phase, Split-System)<65,000 Btu/hACAllSEER = 13June 16, 2008.
   HPAllSEER = 13June 16, 2008.1
Small Commercial Package Air Conditioning and Heating Equipment (Air-Cooled, 3-Phase, Single-Package)<65,000 Btu/hACAllSEER = 13June 16, 2008.1
   HPAllSEER = 13June 16, 2008.1
Small Commercial Package Air Conditioning and Heating Equipment (Air-Cooled)≥65,000 Btu/h and <135,000 Btu/hACNo Heating or Electric Resistance HeatingEER = 11.2January 1, 2010.2
   All Other Types of HeatingEER = 11.0January 1, 2010.2
   HPNo Heating or Electric Resistance HeatingEER = 11.0January 1, 2010.2
   All Other Types of HeatingEER = 10.8January 1, 2010.2
Large Commercial Package Air Conditioning and Heating Equipment (Air-Cooled)≥135,000 Btu/h and <240,000 Btu/hACNo Heating or Electric Resistance HeatingEER = 11.0January 1, 2010.2
   All Other Types of HeatingEER = 10.8January 1, 2010.2
   HPNo Heating or Electric Resistance HeatingEER = 10.6January 1, 2010.2
   All Other Types of HeatingEER = 10.4January 1, 2010.2
Very Large Commercial Package Air Conditioning and Heating Equipment (Air-Cooled)≥240,000 Btu/h and <760,000 Btu/hACNo Heating or Electric Resistance HeatingEER = 10.0January 1, 2010.2
   All Other Types of HeatingEER = 9.8January 1, 2010.2
   HPNo Heating or Electric Resistance HeatingEER = 9.5January 1, 2010.2
   All Other Types of HeatingEER = 9.3January 1, 2010.2
Small Commercial Package Air Conditioning and Heating Equipment (Water-Cooled)<65,000 Btu/hACAllEER = 12.1October 29, 2003.
≥65,000 Btu/h and <135,000 Btu/hACNo Heating or Electric Resistance HeatingEER = 12.1June 1, 2013.
   All Other Types of HeatingEER = 11.9June 1, 2013.
Large Commercial Package Air-Conditioning and Heating Equipment (Water-Cooled)≥135,000 Btu/h and <240,000 Btu/hACNo Heating or Electric Resistance HeatingEER = 12.5June 1, 2014.
   All Other Types of HeatingEER = 12.3June 1, 2014.
Very Large Commercial Package Air-Conditioning and Heating Equipment (Water-Cooled)≥240,000 Btu/h and <760,000 Btu/hACNo Heating or Electric Resistance HeatingEER = 12.4June 1, 2014.
   All Other Types of HeatingEER = 12.2June 1, 2014.
Small Commercial Package Air-Conditioning and Heating Equipment (Evaporatively-Cooled)<65,000 Btu/hACAllEER = 12.1October 29, 2003.
≥65,000 Btu/h and <135,000 Btu/hACNo Heating or Electric Resistance HeatingEER = 12.1June 1, 2013.
   All Other Types of HeatingEER = 11.9June 1, 2013.
Large Commercial Package Air-Conditioning and Heating Equipment (Evaporatively-Cooled)≥135,000 Btu/h and <240,000 Btu/hACNo Heating or Electric Resistance HeatingEER = 12.0June 1, 2014.
   All Other Types of HeatingEER = 11.8June 1, 2014.
Very Large Commercial Package Air Conditioning and Heating Equipment (Evaporatively-Cooled)≥240,000 Btu/h and <760,000 Btu/hACNo Heating or Electric Resistance HeatingEER = 11.9June 1, 2014.
   All Other Types of HeatingEER = 11.7June 1, 2014.
Small Commercial Package Air-Conditioning and Heating Equipment (Water-Source: Water-to-Air, Water-Loop)<17,000 Btu/hHPAllEER = 11.2October 29, 2003.3
≥17,000 Btu/h and <65,000 Btu/hHPAllEER = 12.0October 29, 2003.3
≥65,000 Btu/h and <135,000 Btu/hHPAllEER = 12.0October 29, 2003.3

1And manufactured before January 1, 2017. See Table 3 of this section for updated efficiency standards.

2And manufactured before January 1, 2018. See Table 3 of this section for updated efficiency standards.

3And manufactured before October 9, 2015. See Table 3 of this section for updated efficiency standards.

Table 2 to §431.97—Minimum Heating Efficiency Standards for Air Conditioning and Heating Equipment [Heat Pumps]

[Not including single package vertical air conditioners and single package vertical heat pumps, packaged terminal air conditioners and packaged terminal heat pumps, computer room air conditioners, variable refrigerant flow multi-split air conditioners and heat pumps, and double-duct air-cooled commercial package air conditioning and heating equipment]

Equipment typeCooling capacityEfficiency levelCompliance date: Equipment manufactured starting on .  .  .
Small Commercial Package Air Conditioning and Heating Equipment (Air-Cooled, 3-Phase, Split-System)<65,000 Btu/hHSPF = 7.7June 16, 2008.1
Small Commercial Pacakage Air-Conditioning and Heating Equipment (Air-Cooled, 3-Phase, Single-Package)<65,000 Btu/hHSPF = 7.7June 16, 2008.1
Small Commercial Package Air Conditioning and Heating Equipment (Air-Cooled)≥65,000 Btu/h and <135,000 Btu/hCOP = 3.3January 1, 2010.2
Large Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled)≥135,000 Btu/h and <240,000 Btu/hCOP = 3.2January 1, 2010.2
Very Large Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled)≥240,000 Btu/h and <760,000 Btu/hCOP = 3.2January 1, 2010.2
Small Commercial Packaged Air Conditioning and Heating Equipment (Water-Source: Water-to-Air, Water-Loop)<135,000 Btu/hCOP = 4.2October 29, 2003.3

1And manufactured before January 1, 2017. See Table 4 of this section for updated heating efficiency standards.

2And manufactured before January 1, 2018. See Table 4 of this section for updated heating efficiency standards.

3And manufactured before October 9, 2015. See Table 4 of this section for updated heating efficiency standards.

Table 3 to §431.97—Updates to the Minimum Cooling Efficiency Standards for Air Conditioning and Heating Equipment

[Not including single package vertical air conditioners and single package vertical heat pumps, packaged terminal air conditioners and packaged terminal heat pumps, computer room air conditioners, variable refrigerant flow multi-split air conditioners and heat pumps, and double-duct air-cooled commercial package air conditioning and heating equipment]

Equipment typeCooling capacitySubcategoryHeating typeEfficiency levelCompliance date: Equipment manufactured starting on .  .  .
Small Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled)≥65,000 Btu/h and <135,000 Btu/hACElectric Resistance Heating or No HeatingIEER = 12.9
IEER = 14.8
January 1, 2018.1
January 1, 2023.
   All Other Types of HeatingIEER = 12.7
IEER = 14.6
January 1, 2018.1
January 1, 2023.
   HPElectric Resistance Heating or No HeatingIEER = 12.2
IEER = 14.1
January 1, 2018.1
January 1, 2023.
   All Other Types of HeatingIEER = 12.0
IEER = 13.9
January 1, 2018.1
January 1, 2023.
Large Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled)≥135,000 Btu/h and <240,000 Btu/hACElectric Resistance Heating or No HeatingIEER = 12.4
IEER = 14.2
January 1, 2018.1
January 1, 2023.
   All Other Types of HeatingIEER = 12.2
IEER = 14.0
January 1, 2018.1
January 1, 2023.
   HPElectric Resistance Heating or No HeatingIEER = 11.6
IEER = 13.5
January 1, 2018.1
January 1, 2023.
   All Other Types of HeatingIEER = 11.4
IEER = 13.3
January 1, 2018.1
January 1, 2023.
Very Large Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled)≥240,000 Btu/h and <760,000 Btu/hACElectric Resistance Heating or No HeatingIEER = 11.6
IEER = 13.2
January 1, 2018.1
January 1, 2023.
   All Other Types of HeatingIEER = 11.4
IEER = 13.0
January 1, 2018.1
January 1, 2023.
   HPElectric Resistance Heating or No HeatingIEER = 10.6
IEER = 12.5
January 1, 2018.1
January 1, 2023.
   All Other Types of HeatingIEER = 10.4
IEER = 12.3
January 1, 2018.1
January 1, 2023.
Small Commercial Package Air-Conditioning and Heating Equipment (Air-Cooled, 3-Phase, Split-System)<65,000 Btu/hACAllSEER = 13.0June 16, 2008.
   HPAllSEER = 14.0January 1, 2017.
Small Commercial Package Air-Conditioning and Heating Equipment (Air-Cooled, 3-Phase, Single-Package)<65,000Btu/hACAllSEER = 14.0January 1, 2017.
   HPAllSEER = 14.0January 1, 2017.
Small Commercial Packaged Air-Conditioning and Heating Equipment (Water Source: Water-to-Air, Water-Loop)<17,000 Btu/hHPAllEER = 12.2October 9, 2015.
   ≥17,000 Btu/h and <65,000 Btu/hHPAllEER = 13.0October 9, 2015.
   ≥65,000 Btu/h and <135,000Btu/hHPAllEER = 13.0October 9, 2015.

1And manufactured before January 1, 2023.

Table 4 to §431.97—Updates to the Minimum Heating Efficiency Standards for Air-Cooled Air Conditioning and Heating Equipment [Heat Pumps]

[Not including single package vertical air conditioners and single package vertical heat pumps, packaged terminal air conditioners and packaged terminal heat pumps, computer room air conditioners, variable refrigerant flow multi-split air conditioners and heat pumps, and double-duct air-cooled commercial package air conditioning and heating equipment]

Equipment typeCooling capacityEfficiency level.1Compliance date: Equipment manufactured starting on .  .  .
Small Commercial Package Air Conditioning and Heating Equipment (Air-Cooled, 3-Phase, Split-Sytem)<65,000 Btu/hHSPF = 8.2January 1, 2017.
Small Commercial Package Air Conditioning and Heating Equipment (Air-Cooled, 3-Phase, Single Package)<65,000 Btu/hHSPF = 8.0January 1, 2017.
Small Commercial Package Air Conditioning and Heating Equipment (Water-Source: Water-to-Air, Water-Loop)<135,000 Btu/hCOP = 4.3October 9, 2015.
Small Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled)≥65,000 Btu/h and
<135,000 Btu/h
COP = 3.3
COP = 3.4
January 1, 2018.2
January 1, 2023.
Large Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled)≥135,000 Btu/h and
<240,000 Btu/h
COP = 3.2
COP = 3.3
January 1, 2018.2
January 1, 2023.
Very Large Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled)≥240,000 Btu/h and
<760,000 Btu/h
COP = 3.2January 1, 2018.

1For units tested using the relevant AHRI Standards, all COP values must be rated at 47 °F outdoor dry-bulb temperature for air-cooled equipment.

2And manufactured before January 1, 2023.

Table 5 to §431.97—Minimum Cooling Efficiency Standards for Double-Duct Air-Conditioning and Heating Equipment

Equipment typeCooling capacitySubcategoryHeating typeEfficiency levelCompliance date: Equipment manufactured starting on .  .  .
Small Double-Duct Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled)≥65,000 Btu/h and <135,000 Btu/hACElectric Resistance Heating or No HeatingEER = 11.2January 1, 2010.
   All Other Types of HeatingEER = 11.0January 1, 2010.
   HPElectric Resistance Heating or No HeatingEER = 11.0January 1, 2010.
   All Other Types of HeatingEER = 10.8January 1, 2010.
Large Commercial Double-Duct Packaged Air Conditioning and Heating Equipment (Air-Cooled)≥135,000 Btu/h and <240,000 Btu/hACElectric Resistance Heating or No HeatingEER = 11.0January 1, 2010.
   All Other Types of HeatingEER = 10.8January 1, 2010.
   HPElectric Resistance Heating or No HeatingEER = 10.6January 1, 2010.
   All Other Types of HeatingEER = 10.4January 1, 2010.
Very Large Double-Duct Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled)≥240,000 Btu/h and <300,000 Btu/hACElectric Resistance Heating or No HeatingEER = 10.0January 1, 2010.
   All Other Types of HeatingEER = 9.8January 1, 2010.
   HPElectric Resistance Heating or No HeatingEER = 9.5January 1, 2010.
   All Other Types of HeatingEER = 9.3January 1, 2010.

Table 6 to §431.97—Minimum Heating Efficiency Standards for Double-Duct Air-Cooled Air Conditioning and Heating Equipment

[Heat pumps]

Equipment typeCooling capacityHeating typeEfficiency level1Compliance date: Equipment manufactured starting on ...
Small Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled, Double-Duct)≥65,000 Btu/h and <135,000 Btu/hElectric Resistance Heating or No HeatingCOP = 3.3January 1, 2010.
   All Other Types of HeatingCOP = 3.3January 1, 2010.
Large Commercial Packaged Air-Conditioning and Heating Equipment (Air-Cooled, Double-Duct)≥135,000 Btu/h and <240,000 Btu/hElectric Resistance Heating or No HeatingCOP = 3.2January 1, 2010.
   All Other Types of HeatingCOP = 3.2January 1, 2010.
Very Large Commercial Packaged Air Conditioning and Heating Equipment (Air-Cooled, Double-Duct)≥240,000 Btu/h and <300,000 Btu/hElectric Resistance Heating or No HeatingCOP = 3.2January 1, 2010.
   All Other Types of HeatingCOP = 3.2January 1, 2010.

1For units tested using the relevant AHRI Standards, all COP values must be rated at 47 °F outdoor dry-bulb temperature for air-cooled equipment.

(c) Each non-standard size packaged terminal air conditioner (PTAC) and packaged terminal heat pump (PTHP) manufactured on or after October 7, 2010 must meet the applicable minimum energy efficiency standard level(s) set forth in Table 7 of this section. Each standard size PTAC manufactured on or after October 8, 2012, and before January 1, 2017 must meet the applicable minimum energy efficiency standard level(s) set forth in Table 7 of this section. Each standard size PTHP manufactured on or after October 8, 2012 must meet the applicable minimum energy efficiency standard level(s) set forth in Table 7 of this section. Each standard size PTAC manufactured on or after January 1, 2017 must meet the applicable minimum energy efficiency standard level(s) set forth in Table 8 of this section.

Table 7 to §431.97—Minimum Efficiency Standards for PTAC and PTHP

Equipment typeCategoryCooling capacityEfficiency levelCompliance date: products
manufactured on
and after .  .  .
PTACStandard Size<7,000 Btu/hEER = 11.7October 8, 2012.2
   ≥7,000 Btu/h and ≤15,000 Btu/hEER = 13.8−(0.3 × Cap1)October 8, 2012.2
   >15,000 Btu/hEER = 9.3October 8, 2012.2
Non-Standard Size<7,000 Btu/hEER = 9.4October 7, 2010.
≥7,000 Btu/h and ≤15,000 Btu/hEER = 10.9−(0.213 × Cap1)October 7, 2010.
   >15,000 Btu/hEER = 7.7October 7, 2010.
PTHPStandard Size<7,000 Btu/hEER = 11.9
COP = 3.3
October 8, 2012.
   ≥7,000 Btu/h and ≤15,000 Btu/hEER = 14.0−(0.3 × Cap1)
COP = 3.7−(0.052 × Cap1)
October 8, 2012.
   >15,000 Btu/hEER = 9.5
COP = 2.9
October 8, 2012.
   Non-Standard Size<7,000 Btu/hEER = 9.3
COP = 2.7
October 7, 2010.
   ≥7,000 Btu/h and ≤15,000 Btu/hEER = 10.8−(0.213 × Cap1)
COP = 2.9−(0.026 × Cap1)
October 7, 2010.
   >15,000 Btu/hEER = 7.6
COP = 2.5
October 7, 2010.

1“Cap” means cooling capacity in thousand Btu/h at 95 °F outdoor dry-bulb temperature.

2And manufactured before January 1, 2017. See Table 8 of this section for updated efficiency standards that apply to this category of equipment manufactured on and after January 1, 2017.

Table 8 to §431.97—Updated Minimum Efficiency Standards for PTAC

Equipment typeCategoryCooling capacityEfficiency levelCompliance date: products
manufactured on
and after .  .  .
PTACStandard Size<7,000 Btu/hEER = 11.9January 1, 2017.
   ≥7,000 Btu/h and ≤15,000 Btu/hEER = 14.0−(0.3 × Cap1)January 1, 2017.
   >15,000 Btu/hEER = 9.5January 1, 2017.

1“Cap” means cooling capacity in thousand Btu/h at 95 °F outdoor dry-bulb temperature.

(d)(1) Each single package vertical air conditioner and single package vertical heat pump manufactured on or after January 1, 2010, but before October 9, 2015 (for models ≥65,000 Btu/h and <135,000 Btu/h) or October 9, 2016 (for models ≥135,000 Btu/h and <240,000 Btu/h), must meet the applicable minimum energy conservation standard level(s) set forth in this section.

Table 9 to §431.97—Minimum Efficiency Standards for Single Package Vertical Air Conditioners and Single Package Vertical Heat Pumps

Equipment typeCooling capacitySub-categoryEfficiency levelCompliance date: products manufactured on and
after .  .  .
Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase<65,000 Btu/hAC
HP
EER = 9.0
EER = 9.0
COP = 3.0
January 1, 2010
January 1, 2010
Single package vertical air conditioners and single package vertical heat pumps≥65,000 Btu/h and <135,000 Btu/hAC
HP
EER = 8.9
EER = 8.9
COP = 3.0
January 1, 2010
January 1, 2010
Single package vertical air conditioners and single package vertical heat pumps≥135,000 Btu/h and <240,000 Btu/hAC
HP
EER = 8.6
EER = 8.6
COP = 2.9
January 1, 2010
January 1, 2010

(2) Each single package vertical air conditioner and single package vertical heat pump manufactured on and after October 9, 2015 (for models ≥65,000 Btu/h and <135,000 Btu/h) or October 9, 2016 (for models ≥135,000 Btu/h and <240,000 Btu/h), but before September 23, 2019 must meet the applicable minimum energy conservation standard level(s) set forth in this section.

Table 10 to §431.97—Minimum Efficiency Standards for Single Package Vertical Air Conditioners and Single Package Vertical Heat Pumps

Equipment typeCooling capacitySub-categoryEfficiency levelCompliance date: Products manufactured on and
after .  .  .
Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase<65,000 Btu/hAC
HP
EER = 9.0
EER = 9.0
COP = 3.0
January 1, 2010
January 1, 2010
Single package vertical air conditioners and single package vertical heat pumps≥65,000 Btu/h and <135,000 Btu/hAC
HP
EER = 10.0
EER = 10.0
COP = 3.0
October 9, 2015
October 9, 2015
Single package vertical air conditioners and single package vertical heat pumps≥135,000 Btu/h and <240,000 Btu/hAC
HP
EER = 10.0
EER = 10.0
COP = 3.0
October 9, 2016
October 9, 2016

(3) Each single package vertical air conditioner and single package vertical heat pump manufactured on and after September 23, 2019 must meet the applicable minimum energy conservation standard level(s) set forth in this section.

Table 11 to §431.97—Updated Minimum Efficiency Standards for Single Package Vertical Air Conditioners and Single Package Vertical Heat Pumps

Equipment typeCooling capacitySub-categoryEfficiency levelCompliance date: products manufactured on and
after .  .  .
Single package vertical air conditioners and single package vertical heat pumps, single-phase and three-phase<65,000 Btu/hAC
HP
EER = 11.0
EER = 11.0
COP = 3.3
September 23, 2019.
September 23, 2019.
Single package vertical air conditioners and single package vertical heat pumps≥65,000 Btu/h and <135,000 Btu/hAC
HP
EER = 10.0
EER = 10.0
COP = 3.0
October 9, 2015.
October 9, 2015.
Single package vertical air conditioners and single package vertical heat pumps≥135,000 Btu/h and <240,000 Btu/hAC
HP
EER = 10.0
EER = 10.0
COP = 3.0
October 9, 2016.
October 9, 2016.

(e) Each computer room air conditioner with a net sensible cooling capacity less than 65,000 Btu/h manufactured on or after October 29, 2012, and each computer room air conditioner with a net sensible cooling capacity greater than or equal to 65,000 Btu/h manufactured on or after October 29, 2013, must meet the applicable minimum energy efficiency standard level(s) set forth in this section.

Table 12 to §431.97—Minimum Efficiency Standards for Computer Room Air Conditioners

Equipment typeNet sensible cooling capacityMinimum SCOP efficiencyCompliance date: Products manufactured on and after .  .  .
Downflow unitUpflow unit
Computer Room Air Conditioners, Air-Cooled<65,000 Btu/h
≥65,000 Btu/h and <240,000 Btu/h
2.20
2.10
2.09
1.99
October 29, 2012.
October 29, 2013.
   ≥240,000 Btu/h and <760,000 Btu/h1.901.79October 29, 2013.
Computer Room Air Conditioners, Water-Cooled<65,000 Btu/h
≥65,000 Btu/h and <240,000 Btu/h
2.60
2.50
2.49
2.39
October 29, 2012.
October 29, 2013.
   ≥240,000 Btu/h and <760,000 Btu/h2.402.29October 29, 2013.
Computer Room Air Conditioners, Water-Cooled with a Fluid Economizer<65,000 Btu/h
≥65,000 Btu/h and <240,000 Btu/h
≥240,000 Btu/h and <760,000 Btu/h
2.55
2.45
2.35
2.44
2.34
2.24
October 29, 2012.
October 29, 2013.
October 29, 2013.
Computer Room Air Conditioners, Glycol-Cooled<65,000 Btu/h
≥65,000 Btu/h and <240,000 Btu/h
2.50
2.15
2.39
2.04
October 29, 2012.
October 29, 2013.
   ≥240,000 Btu/h and <760,000 Btu/h2.101.99October 29, 2013.
Computer Room Air Conditioner, Glycol-Cooled with a Fluid Economizer<65,000 Btu/h
≥65,000 Btu/h and <240,000 Btu/h
≥240,000 Btu/h and <760,000 Btu/h
2.45
2.10
2.05
2.34
1.99
1.94
October 29, 2012.
October 29, 2013.
October 29, 2013.

(f) Each variable refrigerant flow air conditioner or heat pump manufactured on or after the compliance date listed in this table must meet the applicable minimum energy efficiency standard level(s) set forth in this section.

Table 13 to §431.97—Minimum Efficiency Standards for Variable Refrigerant Flow Multi-Split Air Conditioners and Heat Pumps

Equipment typeCooling capacityHeating type1Efficiency levelCompliance date: Products manufactured on and after .  .  .
VRF Multi-Split Air Conditioners (Air-Cooled)<65,000 Btu/h
≥65,000 Btu/h and <135,000 Btu/h
All
No Heating or Electric Resistance Heating
13.0 SEER
11.2 EER
June 16, 2008.
January 1, 2010.
   All Other Types of Heating11.0 EERJanuary 1, 2010.
   ≥135,000 Btu/h and <240,000 Btu/hNo Heating or Electric Resistance Heating11.0 EERJanuary 1, 2010.
   All Other Types of Heating10.8 EERJanuary 1, 2010.
   ≥240,000 Btu/h and <760,000 Btu/hNo Heating or Electric Resistance Heating10.0 EERJanuary 1, 2010.
   All Other Types of Heating9.8 EERJanuary 1, 2010.
VRF Multi-Split Heat Pumps
(Air-Cooled)
<65,000 Btu/hAll13.0 SEER
7.7 HSPF
June 16, 2008.
   ≥65,000 Btu/h and <135,000 Btu/hNo Heating or Electric Resistance Heating11.0 EER
3.3 COP
January 1, 2010.
   All Other Types of Heating10.8 EER
3.3 COP
January 1, 2010.
   ≥135,000 Btu/h and <240,000 Btu/hNo Heating or Electric Resistance Heating10.6 EER
3.2 COP
January 1, 2010.
   All Other Types of Heating10.4 EER
3.2 COP
January 1, 2010.
   ≥240,000 Btu/h and <760,000 Btu/hNo Heating or Electric Resistance Heating9.5 EER
3.2 COP
January 1, 2010.
   All Other Types of Heating9.3 EER
3.2 COP
January 1, 2010.
VRF Multi-Split Heat Pumps
(Water-Source)*  *  *
<17,000 Btu/hWithout heat recovery12.0 EER
4.2 COP
October 29, 2012.
October 29, 2003.
   With heat recovery11.8 EER
4.2 COP
October 29, 2012.
October 29, 2003.
   ≥17,000 Btu/h and <65,000 Btu/hAll12.0 EER
4.2 COP
October 29, 2003.
   ≥65,000 Btu/h and <135,000 Btu/hAll12.0 EER
4.2 COP
October 29, 2003.
   ≥135,000 Btu/h and <760,000 Btu/hWithout heat recovery10.0 EER
3.9 COP
October 29, 2013.
   With heat recovery9.8 EER
3.9 COP
October 29, 2013

1VRF Multi-Split Heat Pumps (Air-Cooled) with heat recovery fall under the category of “All Other Types of Heating” unless they also have electric resistance heating, in which case it falls under the category for “No Heating or Electric Resistance Heating.”

[77 FR 28991, May 16, 2012, as amended at 77 FR 76830, Dec. 31, 2012; 80 FR 42664, July 17, 2015; 80 FR 43212, July 21, 2015; 80 FR 56895, Sept. 21, 2015; 80 FR 57500, Sept. 23, 2015; 81 FR 2529, Jan. 15, 2016; 81 FR 53907, Aug. 15, 2016]