Title 46Chapter ISubchapter LPart 129Subpart C → §129.326


Title 46: Shipping
PART 129—ELECTRICAL INSTALLATIONS
Subpart C—Power Sources and Distribution Systems


§129.326   Dual-voltage generators.

If a dual-voltage generator is installed on an OSV—

(a) The neutral of the dual-voltage system must be solidly grounded at the switchboard's neutral bus and be accessible for checking the insulation resistance of the generator; and

(b) Ground detection must be provided that—

(1) For an alternating-current system, complies with §111.05-27 of this chapter; and

(2) For a direct-current system, complies with §111.05-29 of this chapter.