Title 46Chapter ISubchapter KPart 120Subpart C → §120.312


Title 46: Shipping
PART 120—ELECTRICAL INSTALLATION
Subpart C—Power Sources and Distribution Systems


§120.312   Power sources on vessels of more than 19.8 meters (65 feet) in length carrying more than 600 passengers or with overnight accommodations for more than 49 passengers.

A vessel of more than 19.8 meters (65 feet) in length carrying more than 600 passengers or with overnight accommodations for more than 49 passengers must have:

(a) Two generator sets;

(b) An electrical power system that complies with the requirements of §§111.10-4, 111.10-5, and 111.10-9, in subchapter J of this chapter;

(c) A final emergency power source, as defined by §112.01-20 in subchapter J of this chapter, with sufficient capacity to power the loads listed in §112.15-5 in subchapter J of this chapter for three hours; and

(d) The final emergency power source located outside the machinery space.

[CGD 85-080, 61 FR 928, Jan. 10, 1996, as amended by 62 FR 51352, Sept. 30, 1997; USCG-2011-0618, 76 FR 60754, Sept. 30, 2011]