Title 40Chapter ISubchapter DPart 141Subpart T → §141.533


Title 40: Protection of Environment
PART 141—NATIONAL PRIMARY DRINKING WATER REGULATIONS
Subpart T—Enhanced Filtration and Disinfection—Systems Serving Fewer Than 10,000 People


§141.533   What data must my system collect to calculate a disinfection profile?

Your system must monitor the following parameters to determine the total log inactivation using the analytical methods in §141.74 (a), once per week on the same calendar day, over 12 consecutive months:

(a) The temperature of the disinfected water at each residual disinfectant concentration sampling point during peak hourly flow;

(b) If your system uses chlorine, the pH of the disinfected water at each residual disinfectant concentration sampling point during peak hourly flow;

(c) The disinfectant contact time(s) (“T”) during peak hourly flow; and

(d) The residual disinfectant concentration(s) (“C”) of the water before or at the first customer and prior to each additional point of disinfection during peak hourly flow.