Title 40Chapter ISubchapter CPart 60Subpart IIII → Appendix


Title 40: Protection of Environment
PART 60—STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES (CONTINUED)
Subpart IIII—Standards of Performance for Stationary Compression Ignition Internal Combustion Engines


Table 6 to Subpart IIII of Part 60—Optional 3-Mode Test Cycle for Stationary Fire Pump Engines

[As stated in §60.4210(g), manufacturers of fire pump engines may use the following test cycle for testing fire pump engines:]

Mode No.Engine speed1Torque
(percent)2
Weighting
factors
1Rated1000.30
2Rated750.50
3Rated500.20

1Engine speed: ±2 percent of point.

2Torque: NFPA certified nameplate HP for 100 percent point. All points should be ±2 percent of engine percent load value.