Home
gpo.gov
govinfo.gov

e-CFR Navigation Aids

Browse

Simple Search

Advanced Search

 — Boolean

 — Proximity

 

Search History

Search Tips

Corrections

Latest Updates

User Info

FAQs

Agency List

Incorporation By Reference

eCFR logo

Related Resources

Electronic Code of Federal Regulations

We invite you to try out our new beta eCFR site at https://ecfr.federalregister.gov. We have made big changes to make the eCFR easier to use. Be sure to leave feedback using the Feedback button on the bottom right of each page!

e-CFR data is current as of November 24, 2020

Title 40Chapter ISubchapter CPart 60Subpart DDDD → Appendix


Title 40: Protection of Environment
PART 60—STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES (CONTINUED)
Subpart DDDD—Emissions Guidelines and Compliance Times for Commercial and Industrial Solid Waste Incineration Units


Table 7 to Subpart DDDD of Part 60—Model Rule—Emission Limitations That Apply to Energy Recovery Units After May 20, 2011 [Date To Be Specified in State Plan]1

Link to an amendment published at 85 FR 63406, Oct. 7, 2020.

For the air pollutantYou must meet this emission limitation2Using this averaging time3And determining compliance using this method3
Liquid/gasSolids
Cadmium0.023 milligrams per dry standard cubic meterBiomass-0.0014 milligrams per dry standard cubic meter
Coal-0.0017 milligrams per dry standard cubic meter
3-run average (collect a minimum volume of 2 dry standard cubic meters)Performance test (Method 29 at 40 CFR part 60, appendix A-8). Use ICPMS for the analytical finish.
Carbon monoxide35 parts per million dry volumeBiomass-260 parts per million dry volume
Coal-95 parts per million dry volume
3-run average (1 hour minimum sample time per run)Performance test (Method 10 at 40 CFR part 60, appendix A-4).
Dioxins/furans (total mass basis)2.9 nanograms per dry standard cubic meterBiomass-0.52 nanograms per dry standard cubic meter
Coal-5.1 nanograms per dry standard cubic meter
3-run average (collect a minimum volume of 4 dry standard cubic meter)Performance test (Method 23 at 40 CFR part 60, appendix A-7).
Dioxins/furans (toxic equivalency basis)0.32 nanograms per dry standard cubic meterBiomass-0.12 nanograms per dry standard cubic meter
Coal-0.075 nanograms per dry standard cubic meter
3-run average (collect a minimum volume of 4 dry standard cubic meters)Performance test (Method 23 at 40 CFR part 60, appendix A-7).
Hydrogen chloride14 parts per million dry volumeBiomass-0.20 parts per million dry volume
Coal-58 parts per million dry volume
3-run average (for Method 26, collect a minimum of 120 liters; for Method 26A, collect a minimum volume of 1 dry standard cubic meter)Performance test (Method 26 or 26A at 40 CFR part 60, appendix A-8).
Lead0.096 milligrams per dry standard cubic meterBiomass-0.014 milligrams per dry standard cubic meter
Coal-0.057 milligrams per dry standard cubic meter
3-run average (collect a minimum volume of 2 dry standard cubic meters)Performance test (Method 29 at 40 CFR part 60, appendix A-8). Use ICPMS for the analytical finish.
Mercury0.0024 milligrams per dry standard cubic meterBiomass-0.0022 milligrams per dry standard cubic meter
Coal-0.013 milligrams per dry standard cubic meter
3-run average (For Method 29 and ASTM D6784-02 (Reapproved 2008),4 collect a minimum volume of 2 dry standard cubic meters per run. For Method 30B, collect a minimum sample as specified in Method 30B at 40 CFR part 60, appendix A)Performance test (Method 29 or 30B at 40 CFR part 60, appendix A-8) or ASTM D6784-02 (Reapproved 2008).4
Nitrogen oxides76 parts per million dry volumeBiomass-290 parts per million dry volume
Coal-460 parts per million dry volume
3-run average (for Method 7E, 1 hour minimum sample time per run)Performance test (Method 7 or 7E at 40 CFR part 60, appendix A-4).
Particulate matter filterable110 milligrams per dry standard cubic meterBiomass-11 milligrams per dry standard cubic meter
Coal-130 milligrams per dry standard cubic meter
3-run average (collect a minimum volume of 1 dry standard cubic meter)Performance test (Method 5 or 29 at 40 CFR part 60, appendix A-3 or appendix A-8) if the unit has an annual average heat input rate less than or equal to 250 MMBtu/hr; or PM CPMS (as specified in §60.2710(x)) if the unit has an annual average heat input rate greater than 250 MMBtu/hr.
Sulfur dioxide720 parts per million dry volumeBiomass-7.3 parts per million dry volume
Coal-850 parts per million dry volume
3-run average (1 hour minimum sample time per run)Performance test (Method 6 or 6c at 40 CFR part 60, appendix A-4).
Fugitive ashVisible emissions for no more than 5 percent of the hourly observation periodVisible emissions for no more than 5 percent of the hourly observation periodThree 1-hour observation periodsVisible emission test (Method 22 at 40 CFR part 60, appendix A-7).

1The date specified in the state plan can be no later than 3 years after the effective date of approval of a revised state plan or February 7, 2018.

2All emission limitations (except for opacity) are measured at 7 percent oxygen, dry basis at standard conditions. For dioxins/furans, you must meet either the total mass basis limit or the toxic equivalency basis limit.

3In lieu of performance testing, you may use a CEMS or, for mercury, an integrated sorbent trap monitoring system, to demonstrate initial and continuing compliance with an emissions limit, as long as you comply with the CEMS or integrated sorbent trap monitoring system requirements applicable to the specific pollutant in §§60.2710 and 60.2730. As prescribed in §60.2710(u), if you use a CEMS or integrated sorbent trap monitoring system to demonstrate compliance with an emissions limit, your averaging time is a 30-day rolling average of 1-hour arithmetic average emission concentrations.

4Incorporated by reference, see §60.17.

Need assistance?