Title 40Chapter ISubchapter CPart 62Subpart FFF → Appendix


Title 40: Protection of Environment
PART 62—APPROVAL AND PROMULGATION OF STATE PLANS FOR DESIGNATED FACILITIES AND POLLUTANTS
Subpart FFF—Federal Plan Requirements for Large Municipal Waste Combustors Constructed on or Before September 20, 1994


Table 3 to Subpart FFF of Part 62—Municipal Waste Combustor Operating Requirements

Municipal waste combustor technology Carbon monoxide emissions level (parts per million by volume)a Averaging time (hrs)b
Mass burn waterwall1004
Mass burn refractory1004
Mass burn rotary refractory10024
Mass burn rotary waterwall25024
Modular starved air504
Modular excess air504
Refuse-derived fuel stoker20024
Fluidized bed, mixed fuel (wood/refuse-derived fuel)200c24
Bubbling fluidized bed combustor1004
Circulating fluidized bed combustor1004
Pulverized coal/refuse-derived fuel mixed fuel-fired combustor1504
Spreader stoker coal/refuse-derived fuel mixed fuel-fired combustor20024

aMeasured at the combustor outlet in conjunction with a measurement of oxygen concentration, corrected to 7 percent oxygen, dry basis. Calculated as an arithmetic average.

bAveraging times are 4-hour or 24-hour block averages.

c24-hour block average, geometric mean.

[69 FR 42121, July 14, 2004]