Electronic Code of Federal Regulations

We invite you to try out our new beta eCFR site at https://ecfr.federalregister.gov. We have made big changes to make the eCFR easier to use. Be sure to leave feedback using the Feedback button on the bottom right of each page!

e-CFR data is current as of November 23, 2020

Title 40Chapter ISubchapter CPart 62Subpart FFF → Appendix


Title 40: Protection of Environment
PART 62—APPROVAL AND PROMULGATION OF STATE PLANS FOR DESIGNATED FACILITIES AND POLLUTANTS
Subpart FFF—Federal Plan Requirements for Large Municipal Waste Combustors Constructed on or Before September 20, 1994


Table 2 to Subpart FFF of Part 62—Nitrogen Oxides Requirements for Affected Facilities

Municipal waste combustor technologyNitrogen oxides emission limit (parts per million by volume)a
Mass burn waterwall205.
Mass burn rotary waterwall250.
Refuse-derived fuel combustor250.
Fluidized bed combustor180.
Mass burn refractory combustorsNo limit.

aCorrected to 7 percent oxygen, dry basis.